EasyManua.ls Logo

Woodward DSLC-2 - Figure 2-17: Voltage Measuring - Busbar Measuring Inputs, 1 Ph 2 W (Phase-Phase); Table 2-9: Voltage Measuring - Terminal Assignment - Busbar, 1 Ph 2 W (Phase-Phase)

Woodward DSLC-2
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 33/226
'1Ph 2W' Phase-Phase Measuring
Figure 2-17: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-phase)
1Ph 2W
Wiring terminals
Note
Rated voltage (range)
[1] 100 V (50 to 130 V
eff.
)
[4] 400 V (131 to 480 V
eff.
)
5
Measuring range (max.)
[1] 0 to 150 Vac
[4] 0 to 600 Vac
Figure
A
C
---
---
B
D
---
---
DSLC-2 terminal
37
39
---
---
38
40
---
---
Phase
L1 / AØ
L2 / BØ
---
---
L1 / AØ
L2 / BØ
---
---
Table 2-9: Voltage measuring - terminal assignment - busbar, 1Ph 2W (phase-phase)
5 For different voltage systems, different wiring terminals have to be used.Incorrect measurements are possible if both voltage systems use
the same N terminal.

Table of Contents

Related product manuals