Voltage Measuring: Auxiliary Busbar, Parameter Setting '3Ph 3W' (3-phase, 3-wire)
Figure 2-21: Voltage measuring - auxiliary busbar PT windings, 3Ph 3W
Figure 2-22: Voltage measuring - auxiliary busbar measuring inputs, 3Ph 3W
3Ph 3W
Wiring terminals
Note
Rated voltage (range) [1] 120 V (50 to 130 V
eff.
) [4] 480 V (131 to 480 V
eff.
)
7
Measuring range (max.)
[1] 0 to 150 Vac
[4] 0 to 600 Vac
Figure
A
C
E
G
B
D
F
H
DSLC-2 terminal 21 23 25 27 22 24 26 28
Phase
L1 / AØ
L2 / BØ
L3 / CØ
---
L1 / AØ
L2 / BØ
L3 / CØ
---
Table 2-12: Voltage measuring - terminal assignment - auxiliary busbar, 3Ph 3W
7 For different voltage systems, different wiring terminals have to be used.
L1
L2
L3
B2
C2
C1
A1
A2
B1
A
B
C
L1
L2
L3
B1B2
C6
C5
A1
A2
B5B6
A
B
C
C2
C1
A5
A6