Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 60/226 © Woodward
Figure 3-7: ToolKit - home page - generator
If the electrical diagram is shown in “Red” the electrical bar is live. Respectively an electrical diagram shown
in “Green” means a dead bar.
*1
Q: Real reactive load of the generator in kvar.
P: Real load of the generator in kW.
PF: Power factor of the generator.
I: Average current of the generator in A.
Ph-N: Average Phase-neutral voltage of the generator in Volt.
Ph-Ph: Average Phase-phase voltage of the generator in Volt.
f: Real frequency of the generator in Hz.
V: Busbar voltage in Volt.
f: Real frequency of the busbar in Hz.
7726 Process reference: mA - Example of a
configurable engineering unit.
7727 Process signal input: mA - Example of a
configurable engineering unit.
LED: Process PID active – Indicates that the process
control PID is activated.
LED: Remote Reference – Indicates that the load
control or the reactive load control setpoint comes
by analog input.
*1
The parameter Dead bus detection max. volt. (parameter 5820) defines the dead bus condition.
Figure 3-8: ToolKit - home page - segments
This figure indicates which segments in the DSLC-2 / MSLC-2 system are interconnected.
LED: Missing device – Indicates that the configured number of
connected members (DSLC-2 and MSLC-2) is not recognized on
the network.
LED: Centralized alarm – Any configured alarm is active.