Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 64/226 © Woodward
ID
Parameter
CL
Setting range
Default
Description
7514
Auto
resynchroni-
zation
2
Disabled /
Enabled
Disabled
Enables or disables the synchronizer function after achieving syn-
chronization. Synchronization is assumed to have been achieved
if one Reclose delay time interval passes with the CB Auxcon-
tact closed.
Disabled: If this setpoint is set to disabled, the synchronizer is set
to auto-off mode after synchronizing. Has no effect on the control.
Enabled: If the “CB Aux” contact opens and an operating mode is
selected (Run, Check or Permissive), the synchronizer will auto-
matically restart in the selected operating mode. On restart, the
synch timeout timer and close attempts count are reset to their
specified values.
3418
GCB
maximum
closing
attempts
2
1 to 10
5
The maximum number of breaker closing attempts if the Reclose
limit alarm (parameter 7556) is “Enabled”. If “Disabled” this para-
meter is disregarded. See chapter 4, “Synchronizer Description,
for close command information.
7556
Reclose
limit alarm
2
Disabled /
Enabled
Enabled
Enables or disables the alarm generated when reaching the max-
imum close attempts.
4534
Reclose
delay
2
1 to 1000 s
2 s
Is the number of seconds between attempts to close the circuit
breaker. If the CB Auxcontact remains closed for one reclose
delay interval, synchronization is assumed to have occurred. If the
CB Auxcontact opens during the reclose delay interval, it is
considered a failed closed attempt. The DSLC-2 control will re-
main in the selected operating mode (run, check or permissive)
during the reclose delay interval.
7557
Synchronizer
timeout
alarm
2 Disabled /
Enabled
Disabled This setting enables or disables the alarm generated by exceed-
ing the synch timeout interval without achieving synchronization.
3063
Synchronizer
timeout
2
3 to 999 s
60 s
This is the interval over which the synchronizer will attempt to
achieve synchronization. The interval begins when generator vol-
tage is in operating range and either the run or permissive mode
is activated. Failure to get a CB Auxcontact closure within the
specified time will result in a synch timeout alarm. The synchro-
nizer must be set to “Offmode to clear the interval timer and
alarm.
5503
Freq. control
setpoint
ramp
2
0.10 to
60.00 Hz/s
2.50 Hz/s
The slope of the ramp is used to alter the rate at which the con-
troller modifies the setpoint value. The greater the value, the fast-
er the change.
Table 3-10: Parameter synchronizer