Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 87/226
Code level CL2 (Temporary Commissioning Level) No standard password available
This code level grants temporary access to most of the parameters. The password is calculated from the random
number generated when the password is initially accessed. It is designed to grant a user a one-time access to a pa-
rameter without having to provide a reusable password. The user may also change the password for level CL1.
Access granted by this password expires two hours after the password has been entered and the user is returned to
the CL0 level. The password for the temporary commissioning level may be obtained from the vendor.
Code level CL3 (Commissioning Level) Standard password = "
0 0 0 3"
This code level grants complete and total access to most of the parameters. In addition, the user may also change
the passwords for levels CL1, CL2 and CL3. Access granted by this password expires two hours after the pass-
word has been entered and the user is returned to the CL0 level.
NOTE
Once the code level is entered, access to the configuration menus will be permitted for two hours or
until another password is entered into the control. If a user needs to exit a code level, the user would
enter “Details” and select “Log Off”. This will block unauthorized configuration of the control. A user
may return to CL0 by allowing the entered password to expire after two hours or by changing any one
digit on the random number generated on the password screen and entering it into the unit.
It is possible to disable expiration of the password by entering "0000" after the CL1 or CL3 password
has been entered. Access to the entered code level will remain enabled until another password is en-
tered. Otherwise, the code level would expire when loading the standard values (default 0000) via
ToolKit.
ID Parameter CL Setting range Default Description
10415
Basic code
level
1
0000 to 9999
-
The password for the code level "Service (CL1)" is defined in this
parameter.
10414
Temp. com-
missioning
code level
3
0000 to 9999
-
The algorithm for calculating the password for the code level
"Temporary Commissioning (CL2)" is defined in this parameter.
10413
Commission-
ing code
level
3 0000 to 9999 - The password for the code level "Commission (CL3)" is defined in
this parameter.
10412
Temp.
supercomm.
level code
5
0000 to 9999
-
The algorithm for calculating the password for the code level
"Temporary Supercommissioning (CL4)" is defined in this parame-
ter.
10411
Supercom-
missioning
level code
5
0000 to 9999
-
The password for the code level "Supercommissioning (CL5)" is
defined in this parameter.
10416
Random
number for
password
-
Info
-
When somebody enters a temporary password level.
10401
Password for
serial
interface 1
0
0000 to 9999
-
The password for configuring the control via the serial interface #1
must be entered here.
10430
Password for
serial
interface 2
0 0000 to 9999 - The password for configuring the control via the serial interface #2
must be entered here.
10435
Password for
Ethernet
port 2
0
0000 to 9999
-
The password for configuring the control via the Ethernet port #2
(Network B) must be entered here.
10406
Code level
serial
interface 1
-
Info
-
This value displays the code level, which is currently enabled for
access via RS-232 serial interface #1.
10420
Code level
serial
interface 2
-
Info
-
This value displays the code level, which is currently enabled for
access via RS-485 serial interface #2.
10425
Code level
Ethernet
port 2
-
Info
-
This value displays the code level, which is currently enabled for
access via Ethernet port #2 (Network B).