Remote Load Reference Input / Process Reference Input
This analog input can be used for two functionalities:
1. Remote load reference (baseload) input. The input becomes active, if the DI Load Raise”/”Load Low-
erare closed and the DI Process Controlis not closed.
Figure 3-25: ToolKit relevant fields for remote load reference input
The load control interacts with the percentage input value shown in field Reference input (parameter 10177). The
setting on the right side is the scaling for a minimum and maximum load value while displaying the actual kW
setting, which is shown in the field Remote load reference input (parameter 7738).
2. Process reference input. The input becomes active, if the DI Load Raise”/”Load Lowerare closed and
the DI Process Controlis closed.
Figure 3-26: ToolKit relevant fields for remote process reference input
The process control interacts with the percentage input value shown in field Remote reference input (parameter
10117). The setting on the right side will display the actual Process reference (parameter 7726). The process en-
gineering unit will allow you to display a 4 to 20 mA input as a kW value (Example, there are many engineering
units to select). The process signal input and the process reference (remote) will both display the engineering
units selected.
ID
Parameter
CL
Setting range
Default
Description
7711
HW signal
2
0 to 20 mA./
4 to 20 mA./
0 to 10 V./
0 to 5 V./
1 to 5 V
0 to 5 V
Selection of hardware signal range.