Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 92/226 © Woodward
Linear
2 -100.0 to
100.0 %
0.0 % Remote load reference input / process reference input. Linear
scaling: This is the percentage value according to the lowest
Remote load reference input / process reference input. Linear
scaling: This is the percentage value according to the highest
This is the resulting percentage value calculated out of the mini-
mum and maximum scaling as to what the remote input actually
has connected.
This setting is only in use, if the remote load reference input is in
use (see description above). This value is the according kW value
to the percentage value according to the lowest hardware signal
(parameter 4311).This setting is used to display the base load ref-
This setting is only in use, if the remote load reference input is in
use (see description above). This value is the according kW value
to the percentage value according to the highest hardware signal
(parameter 4312). This setting is used to display the base load
This is the resulting kW value calculated out of the minimum and
This is the resulting Process reference value calculated out of the
minimum and maximum scaling, adjusted in parameter 7733 and
The process control engineering units are selected here. With this
input the reference and the real value can be defined in engineer-
ing units for easier customer use.
Process Signal Input
This analog input stands for the process control real signal. The input comes as a hardware signal but the engi-
neering values can be selected here. The process engineering units are adjustable and used for visualizing purpos-
es. The regulation of the process is done with the percentage value.
Figure 3-27: ToolKit – process signal input
4 to 20 mA./
0 to 10 V./
0 to 5 V./
Selection of hardware signal range.