Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 92/226 © Woodward
Linear
ID
Parameter
CL
Setting range
Default
Description
4311
User defined
min display
value
2 -100.0 to
100.0 %
0.0 % Remote load reference input / process reference input. Linear
scaling: This is the percentage value according to the lowest
hardware signal.
4312
User defined
max display
value
2
0.0 to 100 %
100.0 %
Remote load reference input / process reference input. Linear
scaling: This is the percentage value according to the highest
hardware signal.
10117
Remote ref-
erence input
-
Info
-
This is the resulting percentage value calculated out of the mini-
mum and maximum scaling as to what the remote input actually
has connected.
7735
Remote load
ref min
value
2
-999999.9 to
999999.9 kW
0.0 kW
This setting is only in use, if the remote load reference input is in
use (see description above). This value is the according kW value
to the percentage value according to the lowest hardware signal
(parameter 4311).This setting is used to display the base load ref-
erence in kW.
7736
Remote load
ref max
value
2
-999999.9 to
999999.9 kW
500.0 kW
This setting is only in use, if the remote load reference input is in
use (see description above). This value is the according kW value
to the percentage value according to the highest hardware signal
(parameter 4312). This setting is used to display the base load
reference in kW.
7738
Remote load
reference
input
-
Info
-
This is the resulting kW value calculated out of the minimum and
maximum scaling.
7726
Process
reference
-
Info
-
This is the resulting Process reference value calculated out of the
minimum and maximum scaling, adjusted in parameter 7733 and
7734.
7732
Process
engineering
unit
2
kW / °C / kPA /
bar / V / mA
kW
The process control engineering units are selected here. With this
input the reference and the real value can be defined in engineer-
ing units for easier customer use.
Process Signal Input
This analog input stands for the process control real signal. The input comes as a hardware signal but the engi-
neering values can be selected here. The process engineering units are adjustable and used for visualizing purpos-
es. The regulation of the process is done with the percentage value.
Figure 3-27: ToolKit process signal input
ID
Parameter
CL
Setting range
Default
Description
7712
HW signal
2
0 to 20 mA./
4 to 20 mA./
0 to 10 V./
0 to 5 V./
1 to 5 V
1 to 5 V
Selection of hardware signal range.