Manual 37941A DTSC-200A - ATS Controller - Operation
Page 20/37 © Woodward
Application Modes
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The application mode may be configured in the unit (refer to the Configuration Manual 37940 for more infor-
mation). This is only possible in code level 2. The most important features and differences of the three applica-
tion modes are illustrated in the following section. A description of the functions that are possible during each
application mode can be found in the configuration manual (manual 37940).
Util-Util Application Mode
This application mode has the following characteristics:
The ATS controller monitors two mains sources and transfers the load to the secondary source in
case the primary source fails
The ATS controller operates as Master controller
Util-Gen Application Mode
This application mode has the following characteristics:
The ATS controller monitors a mains sources and a generator source and transfers the load to the
generator source in case the mains source fails
The ATS controller operates as Master controller
Gen-Gen Application Mode
This application mode has the following characteristics:
The ATS controller monitors two generator sources and transfers the load to the other source in
case the regular source fails
The ATS controller operates as Slave controller
This application is not a stand-alone application and always combined with another ATS control-
ler in Util-Gen application mode, which operates as Master controller (refer to the Application
Manual 37942 for more information)
Engine operation special cases
In Util-Gen application mode and Gen-Gen application mode the ATS starts and stops an engine. Starting and
stopping is controlled by the state machine described above. However, in some rare situations the start/stop is af-
fected by the breaker state. These are
If a breaker cannot be closed to a generator source (indicated by a corresponding alarm), then the engine
shall not run, it shall either not start or do a stop after cooldown
If a breaker is connected to a generator source and cannot be opened (indicated by a corresponding alarm),
the engine shall continue to run.
If a breaker closing to a generator source is inhibited, and the breaker is not already closed, the engine shall
not run or do a stop after cooldown.