Manual 37941A DTSC-200A - ATS Controller - Operation
© Woodward Page 25/37
Table 3-2 is valid for the following settings:
• Parameter 3424 "Transfer switch type" is configured to "Delayed"
• Parameter 3434 "Use limit sw. OPEN replies" is configured to "NO"
Table 3-2: Limit switch monitoring - truth table for "Delayed" limit switch w/o "Open" replies
Limit switch monitoring is disabled for the following settings:
• Parameter 3424 "Transfer switch type" is configured to "Standard"
• Parameter 3434 "Use limit sw. OPEN replies" is configured to "NO"
Table 3-3 is valid for the following settings:
• Parameter 3424 "Transfer switch type" is configured to "Delayed" Parameter 3434 "Use limit sw. OPEN
replies" is configured to "YES"