Operator Interface
The EGCP-2 Operator Interface is designed for simplicity and redundancy of
function in all operating modes. The backlit LCD screens are used to display
various operating and status information to the operator, as well as for reading
configuration setpoints and alarm information. The backlight on the LCD screen
will stay on whenever the engine’s speed is over 50 RPM. When the engine
shuts down, the backlight will turn off after five minutes. Pressing any key on the
front panel will first turn on the backlight and pressing the key a second time will
perform that function. The backlight will turn off after five minutes of non-use and
the engine is shut down.
NOTE
The EGCP-2 Operator Interface can only be used for unit configuration and
monitoring. Unit start/stop, sync, or mode selection commands can not be
given through the EGCP-2’s front panel.
CAUTION—TRAINED PERSONNEL
An unsafe condition could occur with improper use of these software tools.
Only trained personnel should have access to these tools.
The screens provide eight lines of Status Information, with the option of
displaying four lines of Setpoint tuning or Alarm Log information. These screens
allow the user to monitor and tune related parameters at the same time.
Figure 2-1. Operator Interface
A red Light Emitting Diode (LED) on the face of the control is used to indicate an
alarm condition by flashing repeatedly, and to indicate a shutdown condition by
staying on continuously.