Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 127
Appendix A.
EGCP-2 Setpoint Worksheet
Configuration Menu
Item: Range: Default: As Set Value: Note:
SECURITY
CODE
Min: 0
Max: 9999
**** See Password
section
NETWORK
ADDRESS
Min: 1
Max: 8
1 Only accessible if
configured for
multiple units
NETWORK
PRIORITY
Min: 1
Max: 8
1 Only accessible if
configured for
multiple units
NUMBER OF
POLES
Min: 2
Max: 18
4
NUMBER OF
TEETH
Min: 16
Max: 500
60
SYSTEM
FREQUENCY
Min: 50
Max: 60
60 Hz
RATED SPEED Min:100
Max: 5000
1800 RPM
RATED KW Min: 1
Max: 30000
0 kW
RATED KVA Min: 1
Max: 30000
0 kVA
RATED KVAR Min: 1
Max: 30000
0 kVAR
CT RATIO Min: 5:5
Max: 30000:5
5:5
PT RATIO Min: 1.0:1
Max: 1000.0:1
1.0:1
VOLTAGE
INPUT
Wye line-neutral
Delta line-line
Wye (line-
neutral))
VOLTAGE REF Min: 1
Max: 30000
220 Volts
DISPLAY UNITS
AMERICAN
METRIC
METRIC
SET DATE MM-DD-YY 6-16-2000
SET TIME HH :MM 12 :00 24 Hr. CLOCK
START
SEQUENCING
Enable
Disable
Enable
RELAY #12
FUNCTION
KVA LOAD SWITCH
IDLE/ RATED
SWITCH
KVA LOAD
SWITCH
SPEED BIAS
TYPE
±3 Vdc (WGC)
0.5 TO 4.5 Vdc
(DDEC)
500 Hz PWM (adem)
±3 Vdc
VOLTAGE BIAS
TYPE
±1 Vdc BIAS
±3 Vdc BIAS
±9 Vdc BIAS
±1 Vdc BIAS
CKT BREAKER
CONTROL
Breaker
Contactor
Breaker
OPERATING
MODE
No Parallel
Mains Parallel
No Parallel
NUMBER OF
UNITS
SINGLE
MULTIPLE
SINGLE