Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 129
Item: Range: Default: As Set Value: Note:
REVERSE PWR
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Soft Shutdown
LOSS OF EXCITE Min: -100.0
Max: -5.0
-50.0 %
LOE ALARM Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
REMOTE FAULT1 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled 15 second delay
after crank cut out
speed. Fault 1
timer can add to
this delay.
FAULT1 TIMER Min: 0.0
Max: 30.0
0.0 seconds
REMOTE FAULT2 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled 15 second delay
after crank cut out
speed. Fault 2
timer can add to
this delay.
FAULT2 TIMER Min: 0.0
Max: 30.0
0.0 seconds
REMOTE FAULT3 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Hard Shutdown
FAULT3 TIMER Min: 0.0
Max: 30.0
0.0 seconds
REMOTE FAULT4 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT4 TIMER Min: 0.0
Max: 30.0
0.0 seconds
REMOTE FAULT5 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT5 TIMER Min: 0.0
Max: 30.0
0.0 seconds
REMOTE FAULT6 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT6 TIMER Min: 0.0
Max: 30.0
0.0 seconds