Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 133
Real Load Control Menu
Item: Range: Default: As Set Value: Note:
LOAD CONTROL
MODE
Droop
Normal
Soft Transfer
Normal
LOAD CTRL GAIN Min: 0.001
Max: 100.0
0.01
LOADSHARE
GAIN
Min: 0.1
Max2.0
0.72
LOAD STABILITY Min: 0.0
Max:20.0
2.00
LOAD
DERIVATIVE
Min: 0.0
Max: 20.0
0.20
LOAD CTRL
FILTER
Min: 0.01
Max: 10.0
1.0 Hz
BASE LOAD
REFERENCE
Min: 0.0
Max: 30000.0
50.0 kW
UNLOAD TRIP Min: -10.0
Max: 30000.0
10 kW
LOAD DROOP Min: 0.0
Max: 50.0
5.0 %
LOAD TIME Min: 1.0
Max: 7200.0
10 seconds
UNLOAD TIME Min: 1.0
Max: 7200.0
10 seconds
RAISE LOAD
RATE
Min: 0.01
Max: 100.0
2.00 %/second
LOWER LOAD
RATE
Min: 0.01
Max: 100.0
2.00 %/second
KW LOAD HIGH
LIMIT
Min: 0.0
Max: 30000.0
30 kW
KW HIGH LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Warning
KW LOAD LOW
LIMIT
Min: 0.0
Max: 30000.0
5 kW
KW LOW LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Disabled
KVA SWITCH
LOW
Min: 0
Max: 30000
10 KVA
KVA SWITCH
HIGH
Min: 0
Max: 30000
100 KVA