EGCP-2 Engine Generator Control Package Manual 26086
134 Woodward
Reactive Load Control Menu
Item: Range: Default: As Set Value: Note:
VAR/PF MODE Disabled
PF control
VAR
PF control
VAR/PF GAIN Min: .01
Max: 20.0
1.00
VOLTS RAMP
TIME
Min: 0
Max: 1000
60 sec
VAR/PF
SHARING GAIN
Min: .01
Max: 20.0
1.00
VAR/PF
STABILITY
Min: 0.0
Max: 20.00
1.00
KVAR
REFERENCE
Min: 0
Max: 30000
10 kVAR + = generate
- = absorb
PF REF Min: -0.5 =.5 LEAD
Max: +.5 =.5 LAG
0.0= 1.00 LAG 0.0 = UNITY PF
+ = LAG
- = LEAD
PF DEADBAND Min: 0.0
Max: 1.0
0.005
Process Control Menu
Item: Range: Default: As Set Value: Note:
PROCESS
ACTION
Direct
Indirect
Indirect
PROCESS GAIN Min: 0.001
Max: 100.0
0.10
PROCESS
STABILITY
Min: 0.0
Max: 20.0
1.0 sec
PROCESS
DERIVATIVE
Min: 0.0
Max: 20.0
0.1 sec
PROCESS
DEADBAND
Min: 0.0
Max: 20.0
0.05 mA
PROCESS
DROOP
Min: 0.0
Max: 50.0
0.0 %
PROCESS
FILTER
Min: 0.1
Max: 5.0
1.0 Hz
PROCESS
REFERENCE
Min: 4.0
Max: 20.0
12.0 mA
RAISE RATE Min: 0.01
Max: 20.0
0.1 mA/sec
LOWER RATE Min: 0.01
Max: 20.0
0.1 mA/sec
PROCESS HIGH
LMT
Min: 4.0
Max: 20.0
20.0 mA
PROC HI LMT
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
PROCESS LOW
LMT
Min: 4.0
Max: 20.0
4.0 mA
PROC LO LMT
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled