EasyManua.ls Logo

Woodward EGCP-2 - Transfer Switch Menu

Woodward EGCP-2
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 135
Transfer Switch Menu
Item: Range: Default: As Set Value: Note:
CHECK MAINS
BREAKER
Disabled
Enabled
Enabled
FAST XFER
DELAY
Min: 0.1
Max: 30.0
1.0 sec
MAINS STABLE
DLY
Min: 1
Max: 30000
60 second
GEN STABLE
DLY
Min: 1
Max: 30000
10 second
LOAD SURGE Min: 25.0
Max: 300.0
100.0 % / sec
LOAD SURGE
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN VOLT HIGH
LMT
Min: 50.0
Max: 30000.0
240 volts
MAIN VOLT HIGH
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN VOLT LOW
LMT
Min: 50.0
Max: 30000.0
200 volts
MAIN VOLT LOW
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN FREQ HIGH
LMT
Min: 40.0
Max: 75.0
61.0 Hz
MAIN FREQ HIGH
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN FREQ LOW
LMT
Min: 40.0
Max: 75.0
59.0 Hz
MAIN FREQ LOW
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Disabled
LOM ACTION
DELAY
Min: 0.1
Max: 30.0
0.1 seconds

Table of Contents