EGCP-2 Control Specifications
Woodward Part Numbers:
8406-115 EGCP-2 Engine Generator Control, 150-300 Vac PT input
8406-116 EGCP-2 Engine Generator Control, 50-150 Vac PT input
Power Supply Rating 9–32 Vdc (SELV) Maximum input voltage range
Power Consumption less than or equal 13 W nominal, 20 W maximum
Input Supply Voltage Input Supply Current
12 V (nominal) 1.08 A
24 V (nominal) 542 mA
32 V 406 mA
PT input 50-150 Vac, 8406-116
150-300 Vac, 8406-115
CT input 0–5 Arms
Generator Frequency Range 40–70 Hz
Magnetic Pickup 100–15000 Hz
Discrete Inputs (8) 5 mA source current when CLOSED to Switch Common
(65)
Process input 4–20 mA, 1–5 Vdc
Temperature and pressure inputs 0–200 Ω sensors, 4–20 mA transducer, or 0–5 V
transducer
Speed Bias ±3 Vdc, .5–4.5 Vdc, 5V peak 500 Hz PWM
Voltage Bias ±1 Vdc, ±3 Vdc, ±9 Vdc
Discrete Outputs (Relay Outputs) 10 A, 250 Vac Resistive
1/3 HP, 125 Vac (7.2 Amp, 0.4-0.5 P.F.)
10 Amp, 30 Vdc Resistive
Communication Ports RS-485, RS-422
Ambient Operating Temperature –20 to +70 °C (–4 to +158 °F)(around outside of EGCP-2
Chassis)
Storage Temperature –40 to +105 °C (–40 to +221 °F)
Humidity 95% at +20 to +55 °C (+68 to +131 °F)
Mechanical Vibration SV2 5–2000 Hz @ 4 G and RV1 10–2000 Hz @ .04 G²/Hz
Mechanical Shock US MIL-STD 810C, Method 516.2, Procedure I (basic
design test), Procedure II (transit drop test, packaged),
Procedure V (bench handling)
Equipment Classification Class 1 (grounded equipment)
Air Quality Pollution Degree II
Installation Overvoltage Category III
Ingress Protection Will meet the requirements of IP56 as defined in IEC529
when installed in a suitable atmospherically vented
enclosure. Also meets Type 4 requirements.