EGCP-2 Engine Generator Control Package Manual 26086
16 Woodward
The screen displays the following information:
Alarms: Number of active alarms on the unit.
Unit #: The network address of the unit.
Mains: A graphic display of the mains condition. Two minus symbols (--)
indicates the mains are out of spec, one plus symbol indicates the mains are in
spec, but not declared stable (+-), two plus symbols (++) indicates the mains are
in spec and stable.
Gen: A graphic display of the status of the generator. Two minus symbols (--)
indicates the generator is out of spec, one plus symbol indicates the gen is in
spec, but not declared stable (+-) two plus symbols (++) indicates the generator
is in spec and stable.
Engine: The operating state of the engine.
Engine Control States:
• OFF
• PREGLOW
• CRANK
• RUN
• COOLDOWN
• SPINDOWN
• RETRY
Operating State: Shows if the EGCP-2 is in AUTO or MAN(ual) mode.
Load Control State: Shows the state of the load control logic of the EGCP-2.
The load control states are:
Load Control States:
• OFF
• DROOP
• ISOCHRONOUS
• BASELOAD
• PROCESS
KW: The total KW load on the generator.
Hz: The frequency, in Hertz, of the generator set.
PF: The average three phase power factor of the generator set.
KW-Hrs: The total accumulated kW hours produced by the generator set. This
display automatically switches to MW-Hrs when the kW-Hour value exceeds 10
000.
Run-Time: The total accumulated run time of the generator set.
All the display information will update automatically as operating modes and
conditions to the EGCP-2 change.