EGCP-2 Engine Generator Control Package Manual 26086
18 Woodward
The following is an overview of each of the status menu screens, starting with
engine overview:
Figure 3-4. Engine Overview
HH:MM: 24 hour clock readout.
MM-DD:Date (MM-DD).
Engine: The state of the engine control function.
RPM: Engine rpm.
Battery Volts: Battery Voltage in Vdc.
H2O Temp: Water Temperature in degrees C or F, depending upon the units
selected in configuration.
Oil Press: Oil Pressure in bar, or psi, depending upon the units selected in
configuration.
Gen Breaker: The Status of the generator breaker as provided by the gen cb
aux discrete input.
Gen: The status of the generator. Two minus symbols (--) indicates the generator
is out of spec, one plus symbol indicates the gen is in spec, but not declared
stable (+-) two plus symbols (++) indicates the generator is in spec and stable.