EasyManua.ls Logo

Woodward EGCP-2 - Figure 3-11. Sequencing Menu (Multi-Unit)

Woodward EGCP-2
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 25
The example below is a typical sequencing screen for a 5 unit system.
Figure 3-11. Sequencing Menu (Multi-Unit)
As displayed on the sequencing screen:
Units 1 3, and 5 are on load with their generator breakers closed.
Next On is unit number 2, which has a network priority of 4.
Next Off is unit number 5, which has a network priority of 3.
Master Unit in this system is the unit with the highest priority, which is unit
number one.
NOTE
The sequencing status display when the unit is in Auto and set for Multiple
Units.
Units which have active shutdowns will remove themselves from the
sequencing menu until the shutdown condition(s) are cleared.