EGCP-2 Engine Generator Control Package Manual 26086
26 Woodward
Figure 3-12. ATS (Automatic Transfer Switch) Status.
Mains: A graphic display of the mains condition. Two minus symbols (--)
indicates the mains are out of spec, one plus symbol indicates the mains are in
spec, but not declared stable (+-) two plus symbols (++) indicates mains are in
spec and stable.
Gen: A graphic display of the gen condition. Two minus symbols (--) indicates
the generator is out of spec, one plus symbol indicates the generator is in spec,
but not declared stable (+-) two plus symbols (++) indicates generator is in spec
and stable.
Mains Breaker: The state of the mains breaker as determined by the mains cb
aux discrete input.
Gen Breaker: The state of the generator breaker as determined by the gen cb
aux discrete input.
Synch: The synchronizer control mode.
Mains/Bus: The PT input being sensed by the mains/bus PT input through the
mains disconnect, bus connect discrete output logic.
Bus Dead: An indication of a live or dead local bus as determined by the voltage
on the bus, and state of the generator and mains breaker inputs.
Master Sync Cmd: The master synchronizing and load control bias command
(%).
Master Volt Cmd: The master voltage bias command (%).
NOTE
The master sync and master volt commands are only active in units in AUTO
in multiple unit systems.