Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 41
AmpSeconds accumulate when current is equal to or greater than the
Rated Current
AmpSeconds reset to 0 when current is less than Rated Current
Example:
Overcurrent Level = 160 160 160 Amps
Rated Current = 144 144 144 Amps
Overcurrent Delay = 1.0 10.0 20.0 Seconds
Overcurrent Time = 16 160 320 AmpSeconds
Using Figures 3-21, 3-22, and 3-23 will help you determine where the
Overcurrent Level and Overcurrent Delay should be set for any application.
Overcurrent Alarm
If the Overcurrent Alarm is set for DISABLED, the Overcurrent Level and
Overcurrent Delay will have no effect.
Overcurrent Delay (Numeric)
Configuration
Overcurrent Level = 160 Amps
Rated Current = 144 Amps
Overcurrent Delay = 10 Seconds
Amp/Seconds = 160
Rated
160
Time (seconds)
Overcurrent Trip Zone
Current
(per phase)
144
160
Amp
Seconds
0
10
Figure 3-21. Current goes to 160 Amps, an Alarm or Shutdown will be received
in 10 seconds
Configuration
Overcurrent Level = 160 Amps
Rated Current = 144 Amps
Overcurrent Delay = 10 Seconds
Amp/Seconds = 160
176
Time (seconds)
Current
(per phase)
Overcurrent Trip Zone
160
144
160
Amp
Secs.
0
5 10
Figure 3-22. Current goes to 176 Amps, an Alarm or Shutdown will be received
in 5 seconds