Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 43
Loss of Excitation (LOE) (numeric)
• Set as a percentage of total KVAR load on the generator that can be applied
as a block reactive load to the unit. If control senses changes in KVAR loads
instantly applied greater than this value the LOE alarm triggers.
• Used to indicate loss of field excitation to the generator.
Remote Faults #1 through #6
• Each fault is programmable for:
disabled
warning
visual alarm
audible alarm
soft shutdown
hard shutdown
Remote Faults #1 through #6:
• Each alarm has a programmable time delay (0 to 30000 seconds).
• Each alarm can be set for any of the standard alarm or shutdown levels.
• External Faults #1 and #2 do not start time delay until after gen stable
period has expired.
Engine Control
Preglow Time
• Time of preglow allowed prior to engine crank cycle.
• Maintained through engine cranking.
• Resets after every crank attempt.
Crank Time
• Maximum Allowable Time for Engine Cranking.
Crank Cutout
• Engine rpm level where crank command is canceled.
Crank Delay
• Time between Engine Crank Attempts.
Crank Repeats
• Number of times EGCP-2 will attempt to re-start engine. Cranking attempts
will equal the value of Crank Repeats +1.
Crank Fail
• Alarm Setpoint.
• Activates when Number of Crank Repeats is depleted.
Idle/Rated Speed
• If the Relay #12 output is configured for Idle/Rated switch, this value will set
the speed at which the Idle/Rated Time begins.
• Value should be approx. 10% less than the actual idle speed of the
generator set.