Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 43
Loss of Excitation (LOE) (numeric)
Set as a percentage of total KVAR load on the generator that can be applied
as a block reactive load to the unit. If control senses changes in KVAR loads
instantly applied greater than this value the LOE alarm triggers.
Used to indicate loss of field excitation to the generator.
Remote Faults #1 through #6
Each fault is programmable for:
disabled
warning
visual alarm
audible alarm
soft shutdown
hard shutdown
Remote Faults #1 through #6:
Each alarm has a programmable time delay (0 to 30000 seconds).
Each alarm can be set for any of the standard alarm or shutdown levels.
External Faults #1 and #2 do not start time delay until after gen stable
period has expired.
Engine Control
Preglow Time
Time of preglow allowed prior to engine crank cycle.
Maintained through engine cranking.
Resets after every crank attempt.
Crank Time
Maximum Allowable Time for Engine Cranking.
Crank Cutout
Engine rpm level where crank command is canceled.
Crank Delay
Time between Engine Crank Attempts.
Crank Repeats
Number of times EGCP-2 will attempt to re-start engine. Cranking attempts
will equal the value of Crank Repeats +1.
Crank Fail
Alarm Setpoint.
Activates when Number of Crank Repeats is depleted.
Idle/Rated Speed
If the Relay #12 output is configured for Idle/Rated switch, this value will set
the speed at which the Idle/Rated Time begins.
Value should be approx. 10% less than the actual idle speed of the
generator set.