EGCP-2 Communications Manual 26181
20 Woodward
In the inspector screen the variable name is shown in four parts. First the identity
of the control is listed under the Control column. Then the Category, Block, and
Field are listed. Each variable will have a unique Field name. The Block is the
folder that the variable was located in, and the Category is the top level folder.
This is followed by the real time Value of that variable, and a Description field,
which can be edited by the user to add any notes or comments with the
inspector. For example, the units for a particular variable could be added.
There are three variable types that can be seen in the inspector screen and they
are identified by the following icons:
A variable that is read-only is marked by a set of eyeglasses.
A variable, which is adjustable, is marked with a pencil.
A variable that is only adjustable while the engine is shutdown, is
marked by a shield and pencil.
On the screen above, the middle item LO OIL PRESS LMT has been selected
and, because it is adjustable, a pair of arrows appear to the right of the value.
These arrows can be used to adjust the value by a ±1 % or ±10 % increment. It
is also possible to click the mouse in the Value box and enter a number directly
from the computer keyboard. The adjustment range for this variable is shown at
the bottom of the window. When using the adjustment arrows the changed value
becomes active immediately (no other action is needed). When using direct entry
the adjust arrows are replaced by a button with an equal sign. After the correct
value has been entered, click the equal sign button to activate the entered value.