Woodward EGCP-2 - Figure 7-5 H. Slave Multiple Parallel Process Control Flow Diagram

Woodward EGCP-2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EGCP-2 Engine Generator Control Package Manual 26076
94 Woodward
Auto Input AND
Run With Load
Input AND Test
Loss of Mains
Enabled?
Loss of Mains
Detection Active
Loss of Mains for
>LOM Action
Delay?
Yes
Mains CB AUX
Closed?
Mains Breaker
Reclose Sequence
No
No
No
Yes
Engine
Start
Sequence
Gen Stable?
Close Gen
Breaker Sequence
Run With Load Input
Closed?
Yes
No
Open Gen Breaker
Sequence
Stop Genset
Sequence
Unload Ramp
Base Load Control
Yes
No
Yes
SET Loss of Mains
FLAG
LOM Sequence Shown On
Page #3
Test Input Closed?
No
Yes
Soft Transfer Mode
Enabled
Load Control Mode
Setpoint =
SOFT TRANFER?
No
Yes
To Page
#6
SLAVE Multiple Unit Mains Parallel
Page 5
VIS-093
00-04-24
Figure 7-5h. Slave Multiple Parallel Process Control Flow Diagram