EasyManua.ls Logo

Woodward EGCP-2 - Figure 7-8. Generator Breaker Close Sequence

Woodward EGCP-2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26076 EGCP-2 Engine Generator Control Package
Woodward 101
Gen Breaker Close Sequence
Single No Mains Parallel Unit
Close Gen Breaker
FLAG = TRUE
Switch PT input to
Bus Sensing
Initialize Timers,
Counters
Dead Bus?
(Bus PT Input < 40VAC)
Dead Bus Closing
ENABLED?
Breaker Logic?
Energize Breaker
Open Command
Energize Breaker
Close Command
Gen CB Aux
Input?
Gen Breaker Hold
Timer Expired?
Increment Close
Attempts
Reset Close
Timer
De-Energize
Breaker Open
Command
De-Energize
Breaker Close
Command
Gen Breaker Hold
Timer Expired?
Sync Successful
Set Mode Flag
= IN SYNC
Close Attempts <
Close Attempts Setpoint?
Energize Breaker
Close Command
Breaker Logic?
Start Reclose
Delay Timer
Set Sync
Reclose Alarm
Sync Timeout
Time Expired?
Set Sync
Reclose Alarm
Force Sync
Mode = OFF
Force Sync
Mode = OFF
YES
YES
YES
Sync Timeout
Time Expired?
Set Sync
Reclose Alarm
Force Sync
Mode = OFF
No
Yes
No
No
No
YES
No
YES
No
YES
No
No
No
YES
YES
No
VIS-100
00-04-25
Figure 7-8. Generator Breaker Close Sequence
(Single No Mains Parallel)

Table of Contents

Other manuals for Woodward EGCP-2

Related product manuals