Manual 26076 EGCP-2 Engine Generator Control Package
Woodward 9
SYNC
The SYNC STATUS key shows status information regarding the
generator breaker and utility breaker synchronizer.
KW LOAD
The KW LOAD STATUS key, when pressed, shows the
status information for the KW load control of the EGCP-2.
PF / KVAR
Press the PF/KVAR STATUS key to display VAR/PF Mode
information, as well as three phase generator voltage and current.
SEQUENCE
The SEQUENCE STATUS key provides sequencing
information for multiple unit systems. Single unit systems, and units not in the
AUTO mode will not provide status information in this screen.
ATS
The ATS STATUS key, when pressed, displays the status
information for the Automatic Transfer Switch functions.
Hardware
The EGCP-2 is an integrated control package. All control hardware is contained
in one compact enclosure.
Figure 2-3 is a physical outline drawing with dimensions of the EGCP-2 for
reference during the construction of mounting panels, etc.
To mount the EGCP-2 panel use type M5 x 12mm thread forming screws
(Woodward part number 1029-529).
NOTE
When mounting into an enclosure, make sure the enclosure is vented to
atmosphere through a Type 4 vent tube or unsealed conduit.