EGCP-2 Engine Generator Control Package Manual 26076
16 Woodward
4
3
2
1
Dip Switch # 2
1
2
3
4
Dip Switch # 4
1
2
3
4
Dip Switch # 3
4
3
2
1
Dip Switch # 1
TB 1 TB 2 TB 3 TB 4
TB 5 TB 6 TB7 TB8 TB9
Back View
EGCP-2
DIP Switch Identification
(not to scale).
DIP SWITCHES ARE ACCESSABLE THROUGH HOLES N THE SIDES OF THE
BACK COVER.
SW - 4
RS - 485 Terminations
___________________________
4. 4-20 mA Process Input
3. 123 ohm RS-485 Termination -
2. 123 ohm RS-485 Termination+
1. +5V RS-485
SW - 3
RS-422 Terminations
___________________________
4. No Function.
3. 123 ohm RS-422 Termination -
2. 123 ohm RS-422 Termination+
1. +5V RS-422
SW-2
Temperature Sensor Input Hardware
______________________________
1. 0-200 Sensor.
2. 4-20mA Input Select.
3. 100 ohm dropping resistor Select.
4. 100 ohm dropping resistor Select.
SW-1
Pressure Sensor Input Hardware
______________________________
1. 0-200 Sensor.
2. 4-20mA Input Select.
3. 100 ohm dropping resistor Select.
4. 100 ohm dropping resistor Select.
CLOSED
VIS-143
01-03-16
1 2 3 4
OPEN
1, 3, 4 = OPEN
2 = CLOSED
NOTE OPEN UP, away from PC board.
CLOSED DOWN, toward PC board
Figure 3-4. Dip Switch Location
NOTE
In the drawing above, the switches will do the mentioned functions when in
the CLOSED position.
Input Power
The EGCP-2 accepts any input power source that supplies a voltage within the
9-32 Vdc voltage range. It is expected that the installation of this equipment will
include overcurrent protection between the power source and the EGCP-2. This
overcurrent protection may be accomplished by series connection of properly
rated fuses or circuit breakers (see the Input Power Ratings below for proper
sizing).
Input Power Ratings
Part Number: 8406-115 and 116
Supply Voltage Rating
Nominal Voltage Range: 10–29 Vdc
Maximum Voltage Range: 9–32 Vdc
Maximum Power: 20 W
Typical Power: 13 W
Input Fuse Rating: 5 A (time delay with melting I²t ≥ 100A²sec)
Wire Size: Up to 12 AWG
Holdup Time: 5 milliseconds @ 24 Vdc
Significant inrush currents are possible when current is applied to the EGCP-2
control. The magnitude of the inrush current depends on the power source
impedance, so Woodward cannot specify the maximum inrush current. Time-
delay fuses or circuit breakers must be used to avoid nuisance trips.