EasyManua.ls Logo

Woodward EGCP-2 - Process Import;Export Input; Figure 3-13 A. Wiring Diagram for Process Import;Export Input; Figure 3-13 B. Connecting a KW Transducer Signal to Multiple EGCP-2 S

Woodward EGCP-2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26076 EGCP-2 Engine Generator Control Package
Woodward 27
Process Import/Export Input
The EGCP-2 control can be configured to control any process which is
determined or affected by generator load. The Process Import/Export input is
used by the EGCP-2 control to sense the process level being controlled. This
input can be DIP switch configured to accept either a 4–20 mA or 1–5 dc signal.
Refer to Figure 3-4 for DIP switch location.
Process Input Ratings
Loop Voltage Source: External (4–20 mA), External (1–5 Vdc)
Input Impedance: 249 (4–20 mA), 30 000 (1–5 Vdc)
R
R
R
R
SW4-4
250
87
(-)
(+)
86
Process Import/Export Input
4-20 mA / 1-5 Vdc
Switch SW4-4:
Open for 1-5 volt input @ 30K ohms
Close for 4_20 mA @ 250 ohms
VIS-149
00-08-15
Figure 3-13a. Wiring Diagram for Process Import/Export Input
When connecting a KW transducer signal to multiple EGCP-2s, Woodward
recommends converting the 4–12–20 mA signal to a 1–3–5 Vdc signal by
connecting a 250 resistor across the output of the KW transducer. The Vdc
signal can then be paralleled to all EGCP-2 controls.
+
-
87 8687 8687 86
KW
Transducer
EGCP-2
250 ohm
EGCP-2
EGCP-2
VIS-153
01-05-21
Figure 3-13b. Connecting a KW Transducer Signal to Multiple EGCP-2s
(switch 4-4 is in the OPEN position)