Manual 26076 EGCP-2 Engine Generator Control Package
Woodward 31
+/- 3VDC
.5 to 4.5 VDC
500 Hz PWM
74
(-)
(+)
73
Speed Bias Output
Software Configurable for :
+/- 3VDC
500 Hz PWM
5 to 4.5 VDC
38
(-)
(+)
37
Voltage Bias Output
Software Configurable for:
+/- 1 Vdc
+/- 3 Vdc
+/- 9 Vdc
39
VIS-052a
00-04-19
75
Software Switch
Software Switch
+/- 1VDC
+/- 3VDC
+/-9VDC
Figure 3-15. Wiring Diagram for Speed Bias and Voltage Bias Outputs
Discrete Inputs
Discrete inputs are used by the EGCP-2 control to determine breaker positions
and accept external control commands. Contacts must change state for a
minimum of 40 milliseconds for the control to sense and register a change in
state. All discrete inputs accept dry contacts only, with contact wetting voltage
provided by the EGCP-2 control. The following is a list of the available EGCP-2
Discrete Inputs:
ID # Description
1. Automatic Mode Select
2. Test Engine Mode Select
3. Run with Load Mode Select
4. Voltage Raise
5. Voltage Lower
6. Speed/Load Raise
7. Speed/Load Lower
8. Generator Breaker Aux Contact
9. Utility (Mains) Breaker Aux Contact
10. Process I/E Mode Select
11–16. Configurable Alarm or Shutdown Inputs