EGCP-2 Engine Generator Control Package Manual 26076
40 Woodward
28
Discrete
Output #10
30
29
Generator
Breaker
Trip
VIS-154e
01-06-01
EGCP-2
+ V
Generator
Breaker
Trip (Open) Coil
Figure 3-22. Example Using the NC Contacts to Control the Generator Breakers
Open Coil (DE-ENERGIZE TO OPEN)
No Connection.
9
8
29
30
Gen Breaker Close
Gen Breaker
Trip
Generator
Breaker
Close Coil
Generator
Breaker
Trip Coil
Generator Breaker Configuration Based Logic.
EGCP-2
External Wiring
Connection
External Wiring
Connections
VIS-142a
01-07-11
+V
+V
9
8
29
30
Gen Breaker Close
Gen Breaker
Trip
EGCP-2
+V
Generator
Contactor
Close/Open Coil
Generator Contactor Configuration Based Logic.
Gen Breaker Trip will energize
when in "Auto" and "Gen
Stable Delay" is met.
Figure 3-23. Generator Breaker and Contactor Close and Open Logic