EasyManua.ls Logo

Woodward EGCP-2 - Figure 5-2 B. Single Unit Parallel Overview Flow Diagram

Woodward EGCP-2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EGCP-2 Engine Generator Control Package Manual 26076
62 Woodward
Auto Input AND
Run With Load
Input
Loss of Mains
Enabled?
Loss of Mains
Detection Active
Loss of Mains for
>LOM Action
Delay?
Yes
Mains CB AUX
Closed?
Close Mains
Breaker Sequence
No
No
No
Yes
Engine
Start
Sequence
Gen Stable?
Close Gen
Breaker Sequence
Run With Load Input
Closed?
Yes
No
Open Gen Breaker
Sequence
Stop Genset
Sequence
Unload Ramp
Base Load Control
Yes
No
Yes
SET Loss of Mains
FLAG
Single Parallel Unit
LOM Sequence Shown On
Page #3
VIS-067
00-04-20
Figure 5-2b. Single Unit Parallel Overview Flow Diagram