Manual 26076 EGCP-2 Engine Generator Control Package
Woodward 81
Close Gen Breaker
Sequence
Loss of Mains
FLAG?
No
Yes
Gen Stable?
Set System Run
with Load Flag and
Open Mains
Breaker Sequence
LOM Flag?
Yes
Isoch Load Control
and auto
sequencing
Gen Breaker
Closed?
No
Close Mains
Breaker Sequence
Run/LD
Input?
Yes
Base Load Control
Remove System
Run with Load Flag
and Unload Ramp
Open Gen Breaker
Sequence
Stop Genset
Sequence
No
Yes
No
No
Yes
Process Input?
Yes
Set Master
Process Flag and
System Process
Load Control with
auto sequencing.
No
From Pages 2,4,5 and 7
MASTER Multiple Unit Utility Parallel
Page 3
VIS-080
00-04-24
Figure 7-4c. Master Multiple Parallel Process Control Flow Diagram