Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 107
Adjust the Volts Bias Offset to obtain rated voltage for the generator set.
o Measure the actual generator voltage
o Follow connection procedure in Appendix D for the Voltage
Regulator being used
What Voltage Bias Type to use
Where to preset the Volts Bias Offset
Press the Enter key to save the final Volts Bias Setting
The EGCP-2 control will always reset to the saved Volts Bias Offset value
when the generator breaker is opened.
Whenever the Generator set is started or taken offline, it will control at the
rated voltage when calibrated correctly.
Trim Adj.
Voltage Bias output from EGCP-
Internal Trim adjustment potentiometer
sets effective range of +/- 1 VDC bias
from EGCP-2 control. Usually a +/- 10%
voltage change for the +/-1VDC input
is more than sufficient for good VAR
and PF control.
trim
Volts
Figure 4-35. Typical AVR with Aux Input (Newage SX-440)
Trim Adj.
Voltage Bias outpu
from EGCP-2
Volts
Pot
On regulators without a trim input
such as Leroy Somer AVRs,
an external trim pot must be used
to limit the range of the voltage
bias input from the EGCP-2 control.
Figure 4-36. Typical AVR with External Voltage Adjust Potentiometer