EGCP-2 Engine Generator Control Package Manual 26174
116 Woodward
Suggested Sensors and Calibration Settings
Oil Pressure sensor
Manufacturer VDO
Model 360-xxx
Range 0-80 psi
Dip Switch setting 1-closed 2-open 3-open 4-open
*Oil Pressure Offset –12.07
*Oil Pressure Gain 0.026
Water Temperature sensor
Manufacturer VDO
Model 323-xxx
Range 100-250 deg F.
Dip Switch setting 1-closed 2-closed 3-open 4-open
*Water Temp Offset 123.15
*Water Temp Gain –0.027
*—These are the suggested settings for this sensor only. Woodward
recommends that once installed, with the generator set operating at rated speed
and the temperature stabilized, the high oil pressure and high water temperature
settings be checked against an external water temperature and oil pressure
reading. Adjust the appropriate setting if needed.
NetComm Dropouts
The number of lost or corrupted network communications tolerated by the
receiving unit.
Excess numbers of NetComm Dropouts on network due to faulty wiring,
improper shielding, or improper setup will result in the unit experiencing the
dropouts to flash intermittently in the Sequencing Menu of the EGCP-2.
Typically set at 5 to 10 dropouts.
Unit Calibrated
When set for true, indicates unit has been factory calibrated. Requires Level
4 Security code to change.