EGCP-2 Engine Generator Control Package Manual 26174
212 Woodward
Engine Control Menu
Item: Range: Default:
A
s Set Value: Note:
PREGLOW TIME Min: 0
Max: 1200
5 s
CRANK TIME Min: 0
Max: 240
10 s
CRANK CUTOUT Min: 5
Max: 10000
550 rpm
CRANK DELAY Min: 1
Max: 240
30 s
CRANK
REPEATS
Min: 0
Max: 20
0
CRANK FAIL Warning
Visual Alarm
Audible Alarm
Warning
IDLE SPEED Min: 5
Max: 30000
1200 rpm
IDLE TIME Min: 1
Max: 240
10 s
COOLDOWN
TIME
Min: 0
Max: 2400
120 s
COOLDOWN
LIMIT
Min: 0
Max: 10000
20 kVA
ENGINE RUN
TIME
Min: 0
Max: 32000
0 Hours
MW HOURS Min: 0.0
Max: 32000.0
0.0 MW Hours
OVERSPEED Min: 5.0
Max: 30000.0
1980 rpm
OVERSPEED
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Hard Shutdown
BATT VOLT HI
LMT
Min: 5.0
Max: 50.0
28.5 Volts
BATT VOLT HI
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
BATT VOLT LO
LMT
Min: 5.0
Max: 50.0
10.0 Volts
BATT VOLT LO
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
HI OIL PRESS
LMT
Min: 0.0
Max: 150.0
65 Bar or PSI
HI OIL PRESS
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning

Table of Contents