Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 217
Process Control Menu
Item: Range: Default:
A
s Set Value: Note:
PROCESS
ACTION
Direct
Indirect
Indirect
PROCESS GAIN Min: 0.001
Max: 100.0
0.10
PROCESS
STABILITY
Min: 0.0
Max: 20.0
1.0 s
PROCESS
DERIVATIVE
Min: 0.0
Max: 20.0
0.1 s
PROCESS
DEADBAND
Min: 0.3
Max: 5.0
0.3% % of Full Scale
PROCESS
DROOP
Min: 0.0
Max: 50.0
0.0%
PROCESS
FILTER
Min: 0.1
Max: 5.0
1.0 Hz
PROCESS
REFERENCE
Min: –32,768
Max: 32,767
12.0 *Process Units
RAISE RATE Min: 0.0
Max: 100.0
0.1 %/s
LOWER RATE Min: 0.0
Max: 100.0
0.1 %/s
PROCESS HIGH
LMT
Min: –32,768
Max: 32,767
20.0 *Process Units
PROC HI LMT
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
PROCESS LOW
LMT
Min: –32,768
Max: 32,767
4.0 *Process Units
PROC LO LMT
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
PROCESS UNITS mA
V
kW
MW
kVA
MVA
kVAR
MVAR
PF
Degrees C
Degrees F
PSI
kPA
BAR
mA
PROCESS LOW
VALUE
Min: –32,768
Max: 32,767
4.0
PROCESS HIGH
VALUE
Min: –32,768
Max: 32,767
20.0