EasyManua.ls Logo

Woodward EGCP-2 - Transfer Switch Menu

Woodward EGCP-2
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EGCP-2 Engine Generator Control Package Manual 26174
218 Woodward
Transfer Switch Menu
Item: Range: Default:
A
s Set Value: Note:
CHECK MAINS
BREAKER
Disabled
Enabled
Enabled
FAST XFER
DELAY
Min: 0.1
Max: 30.0
1.0 s
MAINS STABLE
DLY
Min: 1
Max: 30000
60 s
GEN STABLE
DLY
Min: 1
Max: 30000
10 s
LOAD SURGE Min: 25.0
Max: 300.0
100.0%/s
LOAD SURGE
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN VOLT HIGH
LMT
Min: 50.0
Max: 30000.0
240 Volts
MAIN VOLT HIGH
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN VOLT LOW
LMT
Min: 50.0
Max: 30000.0
200 Volts
MAIN VOLT LOW
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN FREQ HIGH
LMT
Min: 40.0
Max: 75.0
61.0 Hz
MAIN FREQ HIGH
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Warning
MAIN FREQ LOW
LMT
Min: 40.0
Max: 75.0
59.0 Hz
MAIN FREQ LOW
ALARM
Disabled
Warning
Loss of Mains
Loss of Mains w/alarms
Disabled
LOM ACTION
DELAY
Min: 0.1
Max: 30.0
0.1 s

Table of Contents