Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 219
Sequencing and Comms Menu
Item: Range: Default:
A
s Set Value: Note:
AUTO
SEQUENCING
Disabled
Enabled
Disabled
AUTO
SEQUENCE
DELAY
Min: 1
Max: 1200
120 s
MAX GEN LOAD Min: 1
Max: 100
60%
NEXT GENSET
DLY
Min: 1
Max: 1200
30 s
RATED LOAD
DELAY
Min: 1
Max: 1200
5 s
MAX START TIME Min: 1
Max: 1200
30 s
MIN GEN LOAD Min: 1
Max: 100
30%
REDUCED LOAD
DLY
Min: 1
Max: 1200
60 s
MAX STOP TIME Min: 1
Max: 1200
60 s
422 PROTOCOL ServLink
Modbus
Upload Set Points
Modbus
Modbus ID Min: 1
Max: 247
1
Modbus Timeout Min: 0.1
Max: 20.0
3.0 s
Modbus Reset False
True
False