Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 21
4
3
2
1
Dip Switch # 2
1
2
3
4
Dip Switch # 4
1
2
3
4
Dip Switch # 3
4
3
2
1
Dip Switch # 1
TB 1 TB 2 TB 3 TB 4
TB 5 TB 6 TB7 TB8 TB9
Back View
EGCP-2
DIP Switch Identification
(not to scale).
DIP SWITCHES ARE ACCESSABLE THROUGH HOLES IN THE SIDES OF THE
BACK COVER.
SW - 4
RS - 485 Terminatio
n
_
____________________
__
4. 4-20 mA Process Input
3. 123 ohm RS-485 Termin
a
2. 123 ohm RS-485 Termin
a
1. +5V RS-485
SW - 3
RS-422 Terminatio
n
_
____________________
_
4. No Function.
3. 123 ohm RS-422 Termin
a
2. 123 ohm RS-422 Termin
a
1. +5V RS-422
SW-2
Temperature Sensor Input Hardware
______________________________
1. 0-200 Sensor.
2. 4-20mA Input Select.
3. 100 ohm dropping resistor Select.
4. 100 ohm dropping resistor Select.
SW-1
Pressure Sensor Input Hardware
______________________________
1. 0-200 Sensor.
2. 4-20mA Input Select.
3. 100 ohm dropping resistor Select.
4. 100 ohm dropping resistor Select.
CLOSED
VIS-143
01-03-16
1 2 3 4
OPEN
1, 3,
2 =
NOTE: OPEN = UP, away from PC b
CLOSED = DOWN, toward P
C
Figure 3-4. Dip Switch Locations
In the drawing above, the switches will do the mentioned functions
when in the CLOSED position.
Input Power
The EGCP-2 accepts any input power source that supplies a voltage within the 9-
32 Vdc voltage range. It is expected that the installation of this equipment will
include overcurrent protection between the power source and the EGCP-2. This
overcurrent protection may be accomplished by series connection of properly
rated fuses or circuit breakers (see the Input Power Ratings below for proper
sizing).
Input Power Ratings
Nominal Voltage Range: 10–29 Vdc
Maximum Voltage Range: 9–32 Vdc
Maximum Input Power: 20 W
Typical Input Power: 13 W @24 Vdc
Input Fuse Rating: 5 A (time delay with melting I²t 100A²sec)
Wire Size: Up to 12 AWG
Holdup Time: 5 milliseconds @ 24 Vdc
Significant inrush currents are possible when current is applied to the EGCP-2
control. The magnitude of the inrush current depends on the power source
impedance, so Woodward cannot specify the maximum inrush current. Time-
delay fuses or circuit breakers must be used to avoid nuisance trips.