EGCP-2 Engine Generator Control Package Manual 26174
34 Woodward
X - May be closed to insert shunt
resistors required to make certain 0-200
ohm sensors more linear.
VIS-050b
01-01-31
R
R
SW2-4
C
R
SW2-3
537.5
100 100
66
+12 Vdc
Coolant
Temperature
Sensor
Input
67
SW2-1
SW 2-2
249
+
-
Input 4-20mA 1-5 Volt 200 Ohm
Sensor
SW2-1 Open Open Closed
SW2-2 Closed Open X
SW2-3 Open Open X
SW2-4 Open Open X
Figure 3-15. Wiring Diagram for Temperature Inputs
When selected for resistive sensor, three additional shunt resistors are provided
to match the impedance range of the given sensor, to provide more range and
accuracy.
These inputs are designed to work with a variety of manufacturer’s sensors.
Sensors can have a Direct or Indirect relationship.
Direct—Increase in Resistance, mA, or volts is an Increase in Pressure
or Temperature.
Indirect—Increase in Resistance, mA, or volts is a Decrease in Pressure
or Temperature.
You must verify how the sensor functions so you can calibrate correctly. The
Calibration menu explains adjusting the Gain and Offset for the different sensors.
Suggested Supplier
Water Temperature Sensor VDO 323-xxx 0-250 deg. F.(Indirect)
Oil Pressure Sensor VDO 360-xxx 0-80 psi (Direct)