Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 55
These 5 items, located in the Transfer Switch menu, can be configured for a Loss
of Mains condition:
Load Surge
Senses a step kW load change (% of Rated Load Set Point per Second) on
generator. LOM indication is immediate (no delay) for this condition.
Mains Frequency Low
Detects Mains Under-frequency condition for at least as long as the LOM Action
Delay set point (seconds).
Mains Frequency High
Detects Mains Over-frequency condition for at least as long as the LOM Action
Delay set point (seconds).
Mains Voltage Low
Detects under-voltage on the mains for at least as long as the LOM Action Delay
set point (seconds).
Mains Voltage High
Detects over-voltage on the mains for at least as long as the LOM Action Delay
set point (seconds).