Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 57
The screen displays the following information:
Alarms: Number of active alarms on the unit.
Unit #: The network address of the unit.
Mains: A graphic display of the mains condition. Two minus symbols (--)
indicate the mains are out of spec, one plus symbol indicates the mains are in
spec, but not declared stable (+-), two plus symbols (++) indicate the mains are
in spec and stable.
Gen: A graphic display of the status of the generator. Two minus symbols (--)
indicate the generator is out of spec, one plus symbol indicates the gen is in
spec, but not declared stable (+-) two plus symbols (++) indicate the generator is
in spec and stable.
Engine: The operating state of the engine.
Engine Control States:
OFF
PREGLOW
CRANK
RUN
COOLDOWN
SPINDOWN
RETRY
Operating State: Shows if the EGCP-2 is in AUTO or MAN (manual) mode.
Load Control State: Shows the state of the load control logic of the EGCP-2.
The load control states are:
Load Control States:
OFF
DROOP
ISOCHRONOUS
BASELOAD
PROCESS
KW: The total kW load on the generator.
Hz: The frequency, in Hertz, of the generator set.
PF: The average three phase power factor of the generator set.
KW-Hrs: The total accumulated kW hours produced by the generator set. This
display automatically switches to MW-Hrs when the kW-Hour value exceeds 10
000. Display is updated every 0.1 MW-Hrs.
Run-Time: The total accumulated run time of the generator set. Display is
updated every run hour.
All the display information will update automatically as operating modes and
conditions to the EGCP-2 change.