EGCP-2 Engine Generator Control Package Manual 26174
80 Woodward
Shutdowns and Alarms
The Shutdowns and Alarms menu is used to configure the generator protection
functions of the EGCP-2.
Each alarm set point can be set for:
Disabled
Warning—LED on control flashes.
Visual Alarm—LED flashes, and Visual Alarm relay energizes.
Audible Alarm—LED flashes, Visual and Audible Alarm relays energize.
Soft Shutdown—LED turns on, Visual and Audible Alarm relays energize,
unit soft unloads, Fuel Solenoid relay de-energizes and cycles through cool
down timer when applicable. Unit removes itself from auto sequencing
order.
Hard Shutdown--Same as above, but immediately opens generator breaker
and de-energizes the fuel solenoid.
Voltage Range Alarm
Alarm/Shutdown point for an excess of voltage bias signal from the EGCP-2
to AVR.
Preset to trigger at ±100% voltage bias output.
Indicates that the AVR is not responding to the voltage bias output as
expected.
Rated Generator Voltage
Generator High Voltage Limit (Voltage Bias Cutout)
Generator Low Voltage Limit (Voltage Bias Cutout)
Operating
Range
Figure 4-20. Generator High/Low Voltage Alarms
Generator Volt High Limit
Sets maximum allowable generator voltage level.
If voltage is above High Limit, generator is not considered stable, and is unfit
for breaker closure.
Generator Volt Low Limit
Sets minimum allowable generator voltage level.
If voltage is below Low Limit, generator is not considered stable, and is unfit
for breaker closure
Voltage Bias will not decrease while generator voltage is below the low limit.