Woodward EGCP-2 - Figure 4-24. Delay Time Is 10 Seconds, Current Goes to 220 A, an Alarm or Shutdown will be Received in 7.5 Seconds

Woodward EGCP-2
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EGCP-2 Engine Generator Control Package Manual 26174
84 Woodward
Rated Current
190
Time (seconds)
Overcurrent Trip Zone
Current
(per phase)
180
0 7.5
150
200
220
Overcurren
Level
15 30
Amp-Seconds
Figure 4-24. Delay Time is 10 Seconds, Current goes to 220 A, an Alarm or
Shutdown will be Received in 7.5 Seconds
Overcurrent Alarm
If the Overcurrent Alarm is set for DISABLED, the Overcurrent Level and
Overcurrent Delay will have no effect.
Reverse Power Level
When the Reverse Power Level is reached, an Instant trip is received.
Configured as a percentage of Rated kW
Range: –1.0 through –50%
Reverse Power Delay
Reverse Power Delay determines the amount of Reverse Power
accumulation needed to cause an Alarm or Shutdown.
Range: 0.1 – 20 seconds
Minimum Reverse Power
The power level must exceed the Minimum Reverse Power continuously for
the calculated delay time before the configured Alarm or Shutdown action is
taken. Reverse power levels above (a less negative or positive power) this
setting will have no effect. When the power level falls below the Minimum
Reverse Power level an accumulation of reverse power is started. As the
power level increases above this level, the accumulated amount will be
reset to zero.
Configured as a percentage of Rated kW
Range: –1.0 through –50%
Configuration Settings
Rated kW 120 kW
Reverse Power Level - 10% (-12 kW)
Reverse Power Delay 2 Seconds
Minimum Reverse Power - 5% (-6 kW)
Reverse Power Value Trip Time
-7 kW 12 seconds
-8 kW 6.5 seconds
-9 kW 4.6 seconds
-12 kW Instant
Table 4-2. Reverse Power Chart