Manual 37128A GCP-20 Series - Genset Control
© Woodward Page 141/190
Parameter 265
freq. low before
start ON
with three-step controllers only
Gas engine; approach low-idle position ON/OFF
If this function is enabled and the control is equipped with a three-step frequency
controller, the command "lower engine speed" is issued for the time configured in
Parameter 266 before the starter is engaged. The low-idle position must either be
equipped with a limiting switch or the engine potentiometer must be equipped with
a slipping clutch to protect the devices. A message is displayed.
CAUTION
The engine starting is delay by means of the low-idle position in the event of emer-
gency power operation.
Parameter 266
action time for
freq. low 000s
with three-step controllers only
Gas engine; approach low-idle position (time) 0 to 999 s
The duration that the "lower engine speed" signal (Parameter 265) is output.