Manual 37278B GCP-30 Series - Genset Control
Page 136/174 © Woodward
kWh Counter
Parameter 316
kWh counter
set in ---
Counter; kWh counter set in ... kWh/MWh
The power produced may be measured in kWh or MWh. The user defined which
scale is desired for the controller with this parameter.
Parameter 317
kWh counter
set 00000---
Counter; kWh counter set for ... 0 to 65,500 kWh/MWh
The user may input values into the kWh/MWh counter (depending on Para-
meter 316) with this parameter. This permits the user to display the correct number
of kWh/MWh for a generator if this controller is used on an older engine or this
controller is to replace an older controller.
NOTE
If the kWh counter is to be changed from the factory default setting, the controller must be in code lev-
el CS2. The counter is set in a two-step procedure due to safety reasons.
The following proceeding is valid:
1. Step: Set and store the desired counter values for the parameters 293 and 294
2. Step: Integrate the stored value by ...
-- Terminate the configuration mode and change to automatic mode
-- Displaying the kWh counter
-- Press and hold the "Digit" push-button for at least 5 seconds