Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 161/174
Parameter Setting range Default value Customer setting
GENERATOR AND MAINS ENVIRONMENT CONFIGURATION
L
Volt.meas./mon.
Ph-neut/Ph-Ph [4/3]
Ph-Ph/Ph-Ph [3/3]
Ph-neut/Ph-neut [4/4]
Ph-neut/Ph-Ph 4/3
3/3
4/4
4/3
3/3
4/4
B + X
Current transf. generator
10 to 7,000/{X} A 500/{X} A
L
Power measuring gen.
singlephase [1]
threephase [3]
threephase 1
3
1
3
B + X
Rated power generator
5 to 9,999 kW 200 kW
B + X
Rated current generator
10 to 7,000 A 300 A
L
Analog in Pmains
OFF/T{x} OFF
L
Analog in Pmains
0 to 20 mA
4 to 20 mA
4 to 20 mA 0-20 mA
4-20 mA
0-20 mA
4-20 mA
L
Analog in Pmains 0%
0 to +/-9,990/0 to +/-6,900 kW -200 kW
L
Analog in Pmains 100%
0 to +/-9,990/0 to +/-6,900 kW 200 kW
L
Current transf. mains
5 to 7,000/{X} A 500 {X} A
B + X
LS 4 mode
ON/OFF OFF on off on off
B + X
Rated power in system
0 to 16,000 kW 1,600 kW
L
Temperature in
Celsius [°C]
Fahrenheit [°F]
Celsius [°C] °C
°F
°C
°F
L
Pressure in
bar
psi
bar bar
psi
bar
psi
Define level 1 code
0 to 9999 0001
Define level 2 code
0 to 9999 0002
CONTROLLER CONFIGURATION
Configure controller
YES/NO NO Y N Y N
Power controller Pset1
C/I/E 0 to 6,900 kW C 50 kW
Power controller Pset2
C/I/E 0 to 6,900 kW C 80 kW
Initial state Frequency
0 to 100 % 50 %
Freq.controller
ON/OFF ON on off on off
f-contr. active at:
0.0 to 70.0 Hz 40.0 Hz
Delay time for f-contr.
0 to 999 s 5 s
Freq.controller ramp
1 to 50 Hz/s 10 Hz/s
RPQ
Frequ.controller droop
0 to 20 % 2 %
L
F/P contr.type
Three-step
Analog
PWM
Analog Three-st.
Analog
PWM
Three-st.
Analog
PWM
Freq.controller deadband
0.02 to 1.00 Hz 0.03 Hz
Freq.controller time pulse>
10 to 250 ms 80 ms
Freq.controller gain Kp
0.1 to 99.9 20.0
F/P contr.output
See table +/-10 V
Level PWM
3.0 to 10.0 V 3.0 V
Stepper sign.frq (min.)
0 to 100 % 0 %
Stepper sign.frq (max.)
0 to 100 % 100 %
Freq.controller gain Kpr
1 to 240 20
Freq.controller reset Tn
0.0 to 60.0 s 1.0 s
Freq.controller derivat.Tv
0.00 to 6.00 s 0.00 s
Starting point voltage
0 to 100 % 50 %
Volt.controller
ON/OFF ON on off on off
Start voltage U control.
12.0 to 100.0 % 75 %
Delayed. Start U contr.
0 to 999 s 3 s
RPQ
Volt.controller droop
0.5 to 20 % 10 %
L
V/Q contr.type
Three-step
Analog
Analog Three-st.
Analog
Three-st.
Analog
Volt.controller dead band
0.1 to 15.0 % 0.9 %
Volt.controller time pulse>
20 to 250 ms 80 ms
Volt.controller gain Kp
0.1 to 99.9 20.0
V/Q contr.output
See table +/-10 V
Stepper sign.vol (min.)
0 to 100 % 0 %
Stepper sign.vol (max.)
0 to 100 % 100 %
Volt.controller gain Kpr
1 to 240 20
Volt.controller reset Tn
0.0 to 60.0 s 1.0 s
Volt.controller derivat.Tv
0.00 to 6.00 s 0.00 s