Manual 37278B GCP-30 Series - Genset Control
Page 162/174 © Woodward
Parameter Setting range Default value Customer setting
CONTROLLER CONFIGURATION
Pow.fact.contr.
ON/OFF OFF on off on off
Pow.fact.contr. setpoint
i0.70 to 1.00 to k0.70 1.00
Pow.fact.contr. dead band
0.5 to 25.0 % 0.5 %
Pow.fact.contr. gain Kp
0.1 to 99.9 20.0
Pow.fact.contr. gain Kpr
1 to 240 20
Pow.fact.contr. reset Tn
0.0 to 60.0 s 1.0 s
Pow.fact.contr. derivat.Tv
0.0 to 6.0 s 0.0 s
Power controller
ON/OFF ON on off on off
power controller ramp
0 to 100 %/s 20 %/s
Power limit P max.
10 to 120 % 100 %
Power limit P min.
0 to 50 % 0 %
Power setpoint external
OFF/ T1 / T2 / T3 OFF OFF
T1
T2
T3
OFF
T1
T2
T3
Analog input
0 to 20 mA
4 to 20 mA
4 to 20 mA 0-20 mA
4-20 mA
0-20 mA
4-20 mA
Ext.setpoint 0mA
C/I/E 0 to 9,999 kW C 0 kW
Ext.setpoint 20mA
C/I/E 0 to 9,999 kW C 200 kW
Power controller dead band
0.1 to 25.0 % 0.5 %
Power controller gain Kp
0.1 to 99.9 20.0
Powercontr. dead band ratio
1.0 to 9.9 2.0
Power controller gain Kpr
1 to 240 20
Power controller reset Tn
0.0 to 60.0 s 1.0 s
Power controller derivat.Tv
0.0 to 6.0 s 0.0 s
Warm up load derivat.Tv
5 to 110 % 15 %
Warm up load time
0 to 600 s 0 s
Active power load-share
ON/OFF ON on off on off
Act. load share factor
10 to 99 % 50 %
Reactive power load share
ON/OFF OFF on off on off
React.load share factor
10 to 99% 50 %
LOAD MANAGEMENT CONFIGURATION
Configure automatic
YES/NO NO Y N Y N
Loadd.start/stop at ter.3
ON/OFF OFF on off on off
Loadd.start/stop at ter.5
ON/OFF OFF on off on off
Minimum load generator
0 to 6,900 kW 15 kW
Add-on delay mains oper.
0 to 999 s 1 s
Shed-off delay mains oper.
0 to 999 s 3 s
Hysteresis add-. on/off op.
0 to 9,999 kW 5 kW
Reserve power mains op.
0 to 9,999 kW 10 kW
Priority of generators
0 to 14 0
Reserve power isol.op.
0 to 9,999 kW 20 kW
Add-on delay isol.op.
0 to 999 s 1 s
Shed-off delay isol.op.
0 to 999 s 4 s
Mains error - stop eng.
ON/OFF OFF on off on off
L
Control via COM X1X5
ON/OFF OFF on off on off
L
Supervision COM X1X5
ON/OFF OFF on off on off
L
Ackn. F2,F3 via COM interf
ON/OFF OFF on off on off
RPQ L
Power On Mode
STOP / MANUAL / AUTO-
MATIC / as before
STOP S M
A b
S M
A b
RPQ L
Interchange Mode in Manual
YES/NO NO Y N Y N