Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 165/174
Parameter Setting range Default value Customer setting
DISCRETE INPUTS CONFIGURATION
Configure dig.inputs
YES/NO NO Y N Y N
Dig.input 1234 function
E/D DDDD
Dig.input 1234 delay
0 to 9 0000
Delayed by 1234 eng.speed
Y/N NNNN
Dig.input 1234 error class
0 to 3 3210
Dig.input 5678 function
E/D DDDD
Dig.input 5678 delay
0 to 9 0000
Delayed by 5678 eng.speed
Y/N NNNN
Dig.input 5678 error class
0 to 3 3111
Dig.input 9ABC function
E/D DDDD
Dig.input 9ABC delay
0 to 9 0000
Delayed by 9ABC eng.speed
Y/N NNNN
Dig.input 9ABC error class
0 to 3 1111
Dig.input DEFG function
E/D DDDD
Dig.input DEFG delay
0 to 9 0000
Delayed by DEFG eng.speed
Y/N NNNN
Dig.input DEFG error class
0 to 3 1111
L
Errortxt.term.34
any
EMERGENCY
OFF
L
Errortxt.term.35
any terminal 35
L
Errortxt.term.36
any terminal 36
L
Errortxt.term.61
any terminal 61
L
Errortxt.term.62
any terminal 62
L
Errortxt.term.63
any terminal 63
L
Errortxt.term.64
any terminal 64
L
Errortxt.term.65
any terminal 65
L
Errortxt.term.66
any terminal 66
L
Errortxt.term.67
any terminal 67
L
Errortxt.term.68
any terminal 68
L
Errortxt.term.69
any terminal 69
L
Errortxt.term.70
any terminal 70
L
Errortxt.term.71
any terminal 71
L
Errortxt.term.72
any terminal 72
L
Errortxt.term.73
any terminal 73
Firing speed by Term. 62
ON/OFF OFF on off on off
Op.mode blocked by Ter.63
ON/OFF OFF on off on off
Breaker logic by Term64
ON/OFF OFF on off on off
Breaker logic:
EXTERNAL [EXT]
PARALLEL [PAR]
OPEN TRANSIT [OPEN]
CLOSED TRANSIT [CLOSE]
INTERCHANGE [INCHG]
EXTERNAL EXT
PAR
OPEN
CLOSE
INCHG
EXT
PAR
OPEN
CLOSE
INCHG
RPQ
f/P setpoint by term.65/66
ON/OFF OFF on off on off
Close GCB asap by Ter.67
ON/OFF OFF on off on off
RPQ
V/Q setpoint by term.67/69
ON/OFF OFF on off on off
Emergency OFF by Ter.68
ON/OFF OFF on off on off
Idle mode by Term.70
ON/OFF OFF on off on off
Function term.6
Sprinkler operation [SO]
Engine enabled [EE]
ext.acknowledgment [ExA]
STOP mode [SM]
Engine blocked [EB]
Start without CB [SwB]
ExA SO
EE
ExA
SM
EB
SwB
SO
EE
ExA
SM
EB
SwB
Start withno GCB cool down
ON/OFF OFF on off on off
Sprinkler shutd. F1 active
ON/OFF OFF on off on off