Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 167/174
Parameter Setting range Default value Customer setting
ANALOG INPUTS CONFIGURATION
Analog input 6 VDO
ON/OFF ON on off on off
L
Name and unit
any Analog 6
Analog input 6 VDO
0 to 5 bar
0 to 10 bar
0 to 5 bar 0-5 bar
0-10 bar
0-5 bar
0-10 bar
Limit warning value
0.0 to 10.0 bar 2.0 bar
Limit shutdown value
0.0 to 10.0 bar 1.0 bar
Delay limit 1/2
0 to 650 s 1 s
L
Monitoring for
High limit mon. [high]
low limit mon. [low]
low limit mon. high
low
high
low
Analog input 7 VDO
ON/OFF ON on off on off
L
Name and unit
any Analog 7
Limit warning value
40 to 120 °C 80 °C
Limit shutdown
40 to 120 °C 90 °C
Delay limit 1/2
0 to 650 s 1 s
L
Monitoring for
High limit mon. [high]
low limit mon. [low]
High limit mon. high
low
high
low
Ana.in 12345678 SV.del.
Y/N NNNNNYNN
Ana.in 12345678 control
Y/N NNNNNNNN
OUTPUT CONFIGURATION
Configure outputs
YES/NO NO Y N Y N
L
Analg.out.12O121 Parameter
0 to 22 1
L
Analg.out.12O121 0-
0 mA
OFF
0 to 20 mA
4 to 20 mA
0 to 20 mA OFF
0-20mA
4-20 mA
OFF
0-20mA
4-20 mA
L
Analg.out.12O121 0%
0 to 9,990 0
L
Analg.out.12O121 100%
0 to 9,990 200
L
Analg.out.122123 Parameter
0 to 22 1
L
Analg.out.122123 0-
0 mA
OFF
0 to 20 mA
4 to 20 mA
0 to 20 mA OFF
0-20mA
4-20 mA
OFF
0-20mA
4-20 mA
L
Analg.out.122123 0%
0 to 9,990 0
L
Analg.out.122123 100%
0 to 9,990 200
L
Assignm.relay 1
See table 1
L
Assignm.relay 2
See table 2
L
Assignm.relay 3
See table 3
L
Assignm.relay 4
See table 4
L
Assignm.relay 5
See table 5
L
Assignm.relay 6
See table 84
L
Assignm.relay 7
See table 85